您的当前位置:首页正文

防雷接地工程施工方案

2022-02-07 来源:伴沃教育
杭州铁路东站枢纽西广场机电安装工程

防雷接地工程专项施工方案

编制: 审核: 审批:

中建三局建设工程股份有限公司(沪)

2011年3月2日

杭州铁路东站西广场·机电安装工程 防雷接地工程施工方案

目 录

目 录 ···································································································· - 1 - 1工程概述 ······························································································· - 2 -

1.1 工程概况 ······················································································· - 2 - 1.2 编制依据 ······················································································· - 2 - 1.3 设计要求 ······················································································· - 3 - 2施工部署 ······························································································· - 5 -

2。1人员组织结构 ··············································································· - 5 -

2。2 施工进度计划 ·············································································· - 5 - 2.3 劳动力计划 ···················································································· - 6 - 2。4 施工机具 ···················································································· - 6 - 2.5 施工材料计划 ················································································· - 6 - 3施工方案 ······························································································· - 6 -

3。1 施工流程 ···················································································· - 6 - 3。2 接地装置安装 ·············································································· - 7 - 3。3 接地端子预留 ·············································································· - 8 - 3。4 防雷引下线安装 ··········································································· - 8 - 3.5 均压环及门窗接地的安装 ································································· - 9 - 3.6 接地电阻测试箱的安装 ···································································· - 9 - 3。7 接闪器施工 ················································································· - 9 - 3。8变配电房及弱电机房接地 ································································ - 9 - 3。9 建筑物等电位连接 ······································································· - 10 - 4。0接地电阻测试 ·············································································· - 10 - 4质量保证措施 ························································································ - 10 -

4.1 质量及工艺标准············································································· - 10 - 4.2 质量通病及防治措施 ······································································ - 12 - 4.3质量保证措施 ················································································ - 13 - 5安全及文明施工 ····················································································· - 13 -

5。1 安全施工 ··················································································· - 13 - 5.2 文明施工 ······················································································ - 14 -

中建三局建设工程股份有限公司(沪) - 1 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

1工程概述

1.1 工程概况

工程建设概况一览表

杭州铁路东站枢纽西广场区工程名称 块配套设施项目 杭州市城东新城建设投资有建设单位 限公司 设计单位 中南建筑设计院股份有限公司 勘察单位 浙江省工程物探勘察院 工程地址 路、新塘路 杭州市江干区新风路交新井浙江明康工程咨询有限公监理单位 司 总包单位 建筑面积 建筑高度/层数 中建三局建设股份有限公司 428600㎡ C座、D座屋面檐口最高处标高均为23.58米.。 质量监督部门 杭州市质监站 合同工期 合同工程投资额 914日历天 140581。8088元(建安总合同额) 以交通集散为核心,以整合国铁、地铁、公交、出租车工程主要功能和社会车辆等多种交通方式或用途 的换乘,实现无缝衔接的交通综合体 1。2 编制依据

1.2。1 业主下发施工图及相关文件

杭州铁路东站枢纽西广场区块配套设施项目招标文件及答疑文件,电气工程

施工图纸;业主、设计、监理和施工单位四方签认的图纸会审记录。 1。2。2我国现行的法律法规、规范、标准及图集

序号 1

名 称

《中华人民共和国建筑法》 编 号 国家法律

中建三局建设工程股份有限公司(沪) - 2 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

2 3 4 5 6 7 《建设工程质量管理条例》 《建筑电气工程施工质量验收规范》 《建筑物防雷设施安装》 《等电位联结安装》 《利用建筑物金属体做防雷及接地装置安装》 《接地装置安装》 国家法规 GB50303-2002 07 D501—1 02 D501—2 03 D501—3 03 D501—4 1.3 设计要求 1.3。1 防雷设计

(1)本建筑按二类防雷建筑物设计; 防雷、电气、消防、弱电和信息

系统共用接地装置。接地电阻要求不大于1欧姆.

(2)接闪器:沿屋顶、女儿墙四周用¢12镀锌圆钢敷设避雷带做接

闪器,网格不大于10m×10m或12m×8m。突出屋面的金属物体(如铁爬梯、水管、透气管等),均与就近的避雷带相连。突出屋面的非金属物体(如烟囱等),加装独立小针,并与就近的避雷带相连.

(3)防侧雷击:建筑物应每层利用周边连通之圈梁钢筋作均压环;并

将地面45米以上外墙上的金属门窗、金属栏杆、幕墙金属构架等与均压环相连接。

(4)防雷引下线:利用外墙柱内2根不小于D16的钢筋为一组作引下

线。引下线间距不大于18米,上与避雷带,下与基础基地装置连接.

(5)防雷电波侵入措施:所有进入建筑物的电缆金属外皮、钢管及各种

金属管道应在进出口处就近与接地装置连接。垂直敷设的金属管道上下端与防雷系统连接。防雷击电磁脉冲保护措施:变压器高低压侧各相装设避雷器;各层主配电箱以及重要设备配电箱,屋顶的配电箱设浪涌保护器,并与防雷分界处作等电位连接;弱电机房配电箱以及进线处设浪涌保护器.

(6)接地装置: 利用基础内钢筋作接地装置,利用结构柱、地梁、桩

基、底板等内部主筋连通作自然接地体,结构基础钢筋(每处直径不小

中建三局建设工程股份有限公司(沪) - 3 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

于16mm,根数不少于4根)。

1。3.2 接地设计

(1)本工程采用共用接地系统,即变压器中性点接地、保护接地及弱电

系统接地等共用防雷基础接地装置.接地电阻不大于1欧姆。

(2)大楼内电气线路采用TN-S接地系统。在变电所内设置总接地点,

用100*100*10的预埋钢板通过柱内主筋与基础钢筋连接。变电所内采用40 *4镀锌扁钢敷设接地干线,于墙上距地300mm明敷。接地干线与柱内预埋的接地连接钢板相焊接.配电柜底座槽钢、变压器外壳、低压PE干线均应与接地干线连接,变电所内设接地端子箱,变压器中性点接地单独采用40*4镀锡扁铜引至接地端子箱并与端子板联接.等电位接地端子板于墙上距地板面300mm安装.做法详国标D563。

(3)各弱电系统工作接地分别采用绝缘铜芯线引至接地端子箱。通过

接地端子箱与基础钢筋连接。

(4)等电位联结:建筑物内所有设备外露可导电部分和装置外可导电部

分均应可靠接地(PE),等电位联接作法详国标《等电位联接安装02D501—2》,具体的等电位联结设计部位及要求:

(1) 建筑物内所有管道井均设置接地端子;

(2) 电梯机房、强弱电机房以及电梯井、强弱电竖井均设置接地

端子;

(3) 用电设备集中的场所(如变配电间、水暖设备用房、配电间、

弱电机房等)均设置接地端子,以供设备、SPD等电位联结用;

(4) 有水暖管道的安装通道设置接地端子;

(5) 接地预留端子选用国家定型产品,离地200mm明装,其与结

构主钢筋引下线的连接采用40x4镀锌扁钢焊接连通; (6) 消防监控中心、弱电中心机房、售票机房等电子信息系统机

中建三局建设工程股份有限公司(沪) - 4 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

房的等电位联结采用M型结构设计,电子信息设备除连接PE线作为保护接地外,还采用两条不同长度的导线以最近距离与等电位联结网络连接.机房内所有设备的金属外壳、金属线槽、各类金属管道、建筑物金属结构、防静电地板等均须进行等电位联结并接地.

(7) 接地电阻检测 本项目每栋建筑物均设置不少于2处接地电

阻测试端子板,接地电阻测试端子板在室外离地0.5米嵌墙暗装,与建筑装饰相一致,并有可靠的防腐措施和明显的接地标志.

2施工部署

2.1人员组织结构

管理组织机构如下图:

安装经理 王涛 技术负责人 张海军 现场负责人 周学军 电气施工员 袁铭骏、兰吉永 施工班组长 金立强 中建三局建设工程股份有限公司(沪) - 5 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

2.2 施工进度计划

防雷接地系统工程工期根据施工前总包方提出的总体施工进度要求进行,配合其他专业施工队伍的进度,在现场具备防雷接地施工条件的前提下,在不影响其他施工的情况下完成防雷接地的施工工作。

2.3 劳动力计划

根据工程各部位的预算用工量和计划工期,在施工期间,根据工程施工进度要求,统一调整技术力量及劳动力。确保施工质量及工程进度。见下表:

序号 1 2 3 工 种 电工 电焊工 综合工 配合阶段(人) 2 2 1 安装高峰阶段(人) 收尾阶段(人) 2 4 2 1 1 2 2.4 施工机具

按照施工计划,将开工前及开工后近期需使用的施工机具及时组织进场,以确保工程按期完成。

见下表: 名称 电焊机(BX1—500型) 切割机 电锤 手枪钻 角向磨光机 剪线钳 接地电阻测试表(ZC29B—2型) 其他工具 单位 台 把 把 把 台 台 只 批 数量 2 1 1 1 4 2 2 1 2.5 施工材料计划

材料计划如下表: 序号 材料名称 规格型号 单位 数量 中建三局建设工程股份有限公司(沪) - 6 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

1 2 3 4 5 镀锌扁钢 钢锌扁钢 镀锌圆钢 镀锌圆钢 钢板 -40*4 -25*4 φ10 φ12 米 米 米 米 / / / / / 3施工方案

100*100*10 KG 3。1 施工流程

人员设备进场 接地装置安装 接地端子预留 防雷引下线安装 均压环及门窗接地安装 接地电阻测试箱安装 接闪器安装 接地电阻测试 变配电房及弱电机房接地 建筑物等电位联结 3.2 接地装置安装

本工程利用建筑物基础钢筋作为接地装置。利用结构柱、地梁、桩基、承台等内部的主筋连通做自然接地体,结构基础钢筋(每处直径不小于16mm,根数不不少于4根)一律采用焊接方式进行可靠连接。

3.2。1 接地网干线内主筋的跨接

根据施工图纸,找出接地网干线所在轴线,待结构底板内的地梁或面筋安装完毕,按接地网所在轴线,挑选4根地梁或面筋内直径大于16mm的主筋做接地干线连通.在有高低落差的地段,横筋与横筋之间用不小于最细一根横筋的圆钢搭接,或用相同截面积的扁钢连接,在主筋螺纹连接处用不小于Φ12的圆钢做跨接处理。并在接地干线纵横交叉处,横筋与纵筋进行连通跨接。

图1 横筋螺纹连接处跨接处理 图2 纵横筋跨接示意图

中建三局建设工程股份有限公司(沪) - 7 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

3.2.2接地网干线与桩基主筋的搭接

于接地干线交叉处,每个承台选2个桩基,每个桩基选2根主筋,利用¢12圆钢引4根桩基主筋与接地干线4根横筋焊接,以保证整个地网可靠连通及满足接地电阻要求.

图3 桩基内主筋与接地横筋的跨接

施工时,密切配合土建施工进度,首先保证横筋是通筋,在土建验筋合格后,在组合柱处横筋与竖筋可靠焊接。焊接时,搭接长度应符合施工工艺的要求。

3。2。3接地装置的电阻测试

接地装置安装完毕后应进行接地电阻的测试工作。接地电阻测试仪采用ZC28B-2型并应取得杭州地方相关检测部门检测合格后,进行测试。测试电阻应不大于1欧姆,如果多次测试未能满足要求,应增设人工接地极,直至接地电阻满足设计要求为止.

图4 接地电阻测试仪的接线图

3。3 接地端子预留

根据接地设计要求,电梯基坑、设备用房等位置需预留接地端子.

3.3。1 定位

根据施工图纸,找出需要设置接地端子的位置.然后从该位置附近找出与之最近的接地主筋。然后利用结构内主筋由接地装置引上至接地端子所在位置。

图5 接地端子扁钢接地点引出示意图

3。3。2 利用圆钢做过渡跨接引出

考虑结构内主筋多为螺纹钢,在与扁钢焊接时,难以保证焊接质量,采取用圆钢过渡跨接。待结构浇筑完毕后露出混泥土部分应做好防腐处理。

图6 利用圆钢过渡跨接

中建三局建设工程股份有限公司(沪) - 8 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

3。4 防雷引下线安装

利用柱内2根直径不小于16mm的结构主筋为一组作引下线。引下线间距不大于18米,上与避雷带,下与基础基地装置连接。

根据施工图纸,找出引下线所在柱子位置。待土建横梁调整完毕后,进行引下线竖筋与接地网横筋的跨接。被作为引下线的结构主筋要做好油漆标示,主筋套丝处应做好圆钢跨接,通长引上至屋面。上与避雷接闪器焊接,下与接地装置焊接。

图7 接地横主筋与引下线的跨接示意图

3。5 均压环及门窗接地的安装

根据设计要求,建筑外围一圈应利用圈梁钢筋做均压环;地面45米以上外墙上的金属门窗、金属栏杆、幕墙金属构架等与均压环相连接。沿建筑外围梁内2根圈梁主筋通长连通,横筋与横筋之间要保持通长连通,在主筋螺纹连接处用不小于Φ12的圆钢做跨接处理。

图8 防雷引下线与被利用做均压环的圈梁主筋的跨接示意图 图9 铝合金窗框的接地做法 图10 金属门框的接地做法 图11 扶手或栏杆接地做法

3。6 接地电阻测试箱的安装

接地测试箱按照图纸位置暗装在距室外地面0。8米处,用¢12镀锌扁钢与防雷引下线焊接后引入接地测试箱,扁钢进箱不少于8cm,扁钢上打不小于ф8mm圆孔后预留镀锌螺栓。测试箱加盖面板,做出接地标志。

图12 暗装接地电阻测试箱做法

3。7 接闪器施工

本工程属二类防雷建筑物,天面采用避雷带(明敷)及屋面板内结

中建三局建设工程股份有限公司(沪) - 9 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

构主筋组成的避雷网格(间距不超过10m×10m或12m×8m)防止直击雷,明敷避雷带采用Φ12镀锌圆钢,支持卡间距不超过1.5m转弯处不超过0.5m,避雷带及避雷网格均须与防雷引下线做好焊接连通.

3。8变配电房及弱电机房接地

根据设计图纸要求,弱电机房和配电室做均压等电位连接,沿室内周围敷设一圈40X4热镀锌扁钢作为均压带,室内各接地点就近与均压带连接,形成M型接地。因此,需要事先向室内引入接地点(不少于两点),并保证接地点在墙面及地板完成后还能找出。

3。9 建筑物等电位连接

(1)公用设施的上、下水、煤气等金属管道、建筑物金属结构采用—40×4镀锌扁钢由总等电位箱(MEB)引至进户钢管处,采用等电位卡子与钢管连接.并在连接处引出-40x4扁钢引至接地母带与其可靠焊接。

(2) 户内卫生间局部等电位箱采用-25×4镀锌扁钢,由最近处接地干线焊接引至卫生间局部等电位箱,扁钢与箱内铜排采用ф8螺栓连接。局部等电位箱按照图纸位置暗装在距地面0。3米处。

4.0接地电阻测试

在防雷接地网系统连接形成后,接地电阻进行测试,要求测试电阻不大于1欧姆。并做好相应的记录。然后申请杭州市防雷检测站进行测试验收。

4质量保证措施

4。1 质量及工艺标准 4。1.1 钢材连接搭接倍数要求

钢质接地装置宜采用焊接连接,其搭接长度应符合下列规定:

中建三局建设工程股份有限公司(沪) - 10 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

1、扁钢与扁钢搭接为扁钢宽度的2倍,三面施焊; 2、圆钢与圆钢搭接为圆钢直径的6倍,双面施焊; 3、圆钢与扁钢搭接为圆钢直径的6倍,双面施焊;

4、扁钢和圆钢与钢管、角钢互相焊接时,除应在接触部位两侧施焊外,还应增加圆钢搭接件;

5、焊接部位除埋在混凝土外均作防腐处理。

接地装置连接应可靠,连接处不应松动、脱焊、接触不良.均压环与金属管道等自然接地体的连接,应采用焊接.如焊接有困难时,可采用卡箍连接,但应有良好的导电性。

4.1。2 各类焊接的要求

a) 平焊 

选择合适的焊接工艺,焊条直径,焊接电流,焊接速度,焊接电弧

长度等,通过焊接工艺试验验证. 

清理焊口:焊前检查坡口、组装间隙是否符合要求,定位焊是否

牢固,焊缝周围不得有油污、锈物。 

烘焙焊条应符合规定的温度与时间,从烘箱中取出的焊条,放在

焊条保温桶内,随用随取。 

焊接电流:根据焊件厚度、焊接层次、焊条型号、直径、焊工熟

练程度等因素,选择适宜的焊接电流。 

引弧:角焊缝起落弧点应在焊缝端部,宜大于10mm,不应随便

打弧,打火引弧后应立即将焊条从焊缝区拉开,使焊条与构件间保持2~4mm间隙产生电弧。对接焊缝及对接和角接组合焊缝,在焊缝两端设引弧板和引出板,必须在引弧板上引弧后再焊到焊缝区,中途接头则应在焊缝接头前方15~20mm处打火引弧,将焊件预热后再将焊条退回到焊缝起始处,把熔池填满到要求的厚度后,方可向前施焊。 

焊接速度:要求等速焊接,保证焊缝厚度、宽度均匀一致,从面

罩内看熔池中铁水与熔渣保持等距离(2~3mm)为宜。 

焊接电弧长度:根据焊条型号不同而确定,一般要求电弧长度稳

中建三局建设工程股份有限公司(沪) - 11 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

定不变,酸性焊条一般为3~4mm,碱性焊条一般为2~3mm为宜。 

焊接角度:根据两焊件的厚度确定,焊接角度有两个万面,一是焊

条与焊接前进方向的夹角为60~75°;二是焊条与焊接左右夹角有两种情况,当焊件厚度相等时,焊条与焊件夹角均为45°;当焊件厚度不等

时,焊条与较厚焊件一侧夹角应大于焊条与较薄焊件一侧夹角。 

收弧:每条焊缝焊到末尾,应将弧坑填满后,往焊接方向相反的

方向带弧,使弧坑甩在焊道里边,以防弧坑咬肉。焊接完毕,应采用气割切除弧板,并修磨平整,不许用锤击落. 

清渣:整条焊缝焊完后清除熔渣,经焊工自检(包括外观及焊缝

尺寸等)确无问题后,方可转移地点继续焊接. b) 立焊:    

基本操作工艺过程与平焊相同,但应注意下述问题: 在相同条件下,焊接电源比平焊电流小10%~15%。 采用短弧焊接,弧长一般为2~3mm。

焊条角度根据焊件厚度确定。两焊件厚度相等,焊条与焊条左右

方向夹角均为45°;两焊件厚度不等时,焊条与较厚焊件一侧的夹角应大于较薄一侧的夹角。焊条应与垂直面形成60°~80°角,使电弧略向上,吹向熔池中心. 

收弧:当焊到末尾,采用排弧法将弧坑填满,把电弧移至熔池中

央停弧。严禁使弧坑甩在一边。为了防止咬肉,应压低电弧变换焊条角度,使焊条与焊件垂直或由弧稍向下吹。 c) 横焊: 

基本与平焊相同,焊接电流比同条件平焊的电流小10%~15%,

电弧长2~4mm。焊条的角度,横焊时焊条应向下倾斜,其角度为70°~80°,防止铁水下坠。根据两焊件的厚度不同,可适当调整焊条角度,焊条与焊接前进方向为70°~90°。 d) 仰焊

基本与立焊、横焊相同,其焊条与焊件的夹角和焊件厚度有关,焊条与焊接方

向成70°~80°角,宜用小电流、短弧焊接。

中建三局建设工程股份有限公司(沪) - 12 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

4。2 质量通病及防治措施

1、尺寸偏差

扁钢焊接时应严格控制其相对位置,扁钢组对应有专人进行,合格后方准焊接. 2、焊瘤

a)熔池下部出现“小鼓肚”时,可利用焊条左右摆动和挑弧动作加以控制. b)在搭接接头立焊时,焊接电流应比平焊适当减少,焊条左右摆动时在中间部位走的快些,两边稍慢些. 3、咬边

选用合适的电流,避免电流过大。操作时电弧不能拉的过长,并控制好焊条的角度和运弧的方法。

4、引上线的制作有专人负责,连接要同侧、同标高.色带宽度、方向一致。 5、过变形缝、沉降缝处的接地干线及避雷带要做补偿处理。

4。3质量保证措施

4。1.1按照国家有关安装工程施工及验收规范以及杭州市有关规定进行验收,按“建筑安装工程质量评定统一标准(GBJ300—88)”进行质量评定。

4。1。2 必须严格按图纸及施工方案施工,施工方案必须经监理批准. 4.1.3 对施工班组进行技术交底,必须交到每一个操作工人。

4.1。4 每道工序完成后,必须经过自检合格后,报请相关工长验收,工长验收合格后,请质量员验收,质量员验收合格后,报请监理工程师验收,合格后,方可进行下一道工序的施工。同时,班组间应进行交接检,交接检后方可进入下一道工序施工.

4。1。5 土建砼浇筑前,必须接到有机电部经理签字的工序交接单后方可进行砼浇筑。

4。1。6 隐蔽工程必须经过质量员,业主,监理及设计单位验收合格并签字后方可隐蔽。

4.1.7 材料进场前必须提供相应的样品,经监理及业主批准后方可进场。进场后经相关责任师、监理、业主验收合格后方可用于施工,同时应提供相应产品检测报告及合格证等。

中建三局建设工程股份有限公司(沪) - 13 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

5安全及文明施工

5.1 安全施工

5。1。1 工人进场必须接受项目经理部组织的安全教育及安全考核. 5。1.2 必须对工人进行安全交底,必须有每一个工人的签名. 5.1.3 每天上班前应开班前会,并有记录。

5。1.4 各项作业指挥及操作必须严格按照国家、浙江省、杭州市、公司及项目经理部有关的安全法律、法规、操作规程及规章制度执行.

5.1。5 进入现场必须戴安全帽,系好帽带,穿安全鞋。高空作业必须系安全带。

5。1.6 施工地点及附近的洞口必须封堵,防止高空坠落。 5。1。7 施工现场严禁吸烟,严禁饮酒,不许打架,戏闹. 5。1.8 不许翻越栏杆。严禁从高处向下扔东西。

5。1。9 现场接电必须由专职维护电工进行,严禁私拉乱接。 5。1。10 电线、电缆等不许拖地.

5。1。11 使用手持电动工具前必须检查其性能,保证良好. 5.1。12 特种作业必须持证上岗.

5.1.13 电气焊施工前必须开动火证,有专人看火,带灭火器。 5.1.14 电焊机不许放置在雨中及潮湿地面上。电焊机必须双线到位. 5.1。15 潮湿地点作业应穿绝缘胶鞋。 5。1。16 施工照明必须使用36V低压电。

5。2 文明施工

5。2。1 进入施工现场必须佩带出入证。 5。2.2 进入现场应衣帽整齐。 5.2.3 施工现场严禁随地大小便。

5.2.4 施工完毕应作到“工完场清”。不许乱丢垃圾。 5。2。5 施工现场应做好自身及其他专业的成品保护工作.

中建三局建设工程股份有限公司(沪) - 14 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

5。2.6 施工材料应设置专门仓库或放置在指定堆放场地上,严禁四处乱堆材料。

5。2。7 材料应码放整齐,并挂好标识牌。

中建三局建设工程股份有限公司(沪) - 15 -

杭州铁路东站西广场·机电安装工程 防雷接地工程施工方案

目 录

目 录 ···································································································· - 1 - 1工程概述 ······························································································· - 2 -

1.1 工程概况 ······················································································· - 2 - 1。2 编制依据 ···················································································· - 2 - 1.3 设计要求 ······················································································· - 3 - 2施工部署 ······························································································· - 5 -

2。1人员组织结构 ··············································································· - 5 -

2.2 施工进度计划 ················································································· - 5 - 2。3 劳动力计划 ················································································· - 6 - 2。4 施工机具 ···················································································· - 6 - 2。5 施工材料计划 ·············································································· - 6 - 3施工方案 ······························································································· - 6 -

3.1 施工流程 ······················································································· - 6 - 3。2 接地装置安装 ·············································································· - 7 - 3.3 接地端子预留 ················································································· - 8 - 3。4 防雷引下线安装 ··········································································· - 8 - 3。5 均压环及门窗接地的安装 ······························································· - 9 - 3.6 接地电阻测试箱的安装 ···································································· - 9 - 3.7 接闪器施工 ···················································································· - 9 - 3。8变配电房及弱电机房接地 ································································ - 9 - 3。9 建筑物等电位连接 ······································································· - 10 - 4.0接地电阻测试 ················································································ - 10 - 4质量保证措施 ························································································ - 10 -

4。1 质量及工艺标准 ·········································································· - 10 - 4.2 质量通病及防治措施 ······································································ - 12 - 4。3质量保证措施 ·············································································· - 13 - 5安全及文明施工 ····················································································· - 13 -

5。1 安全施工 ··················································································· - 13 - 5。2 文明施工 ··················································································· - 14 -

中建三局建设工程股份有限公司(沪) - 1 -

杭州铁路东站西广场·机电安装工程 防雷接地工程施工方案

1工程概述

1。1 工程概况

工程建设概况一览表

杭州铁路东站枢纽西广场区工程名称 块配套设施项目 杭州市城东新城建设投资有建设单位 限公司 设计单位 中南建筑设计院股份有限公司 勘察单位 浙江省工程物探勘察院 工程地址 路、新塘路 杭州市江干区新风路交新井浙江明康工程咨询有限公监理单位 司 总包单位 建筑面积 建筑高度/层数 中建三局建设股份有限公司 428600㎡ C座、D座屋面檐口最高处标高均为23。58米。。 质量监督部门 杭州市质监站 合同工期 合同工程投资额 914日历天 140581。8088元(建安总合同额) 以交通集散为核心,以整合国铁、地铁、公交、出租车工程主要功能和社会车辆等多种交通方式或用途 的换乘,实现无缝衔接的交通综合体 1.2 编制依据

1。2.1 业主下发施工图及相关文件

杭州铁路东站枢纽西广场区块配套设施项目招标文件及答疑文件,电气工程施工图

纸;业主、设计、监理和施工单位四方签认的图纸会审记录。 1。2。2我国现行的法律法规、规范、标准及图集

序号 1 2 名 称 《中华人民共和国建筑法》 《建设工程质量管理条例》 编 号 国家法律 国家法规

中建三局建设工程股份有限公司(沪) - 2 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

3 4 5 6 7 《建筑电气工程施工质量验收规范》 《建筑物防雷设施安装》 《等电位联结安装》 《利用建筑物金属体做防雷及接地装置安装》 《接地装置安装》 GB50303—2002 07 D501—1 02 D501—2 03 D501—3 03 D501—4 1.3 设计要求 1.3。1 防雷设计

(1)本建筑按二类防雷建筑物设计; 防雷、电气、消防、弱电和信息系统共用

接地装置。接地电阻要求不大于1欧姆.

(2)接闪器:沿屋顶、女儿墙四周用¢12镀锌圆钢敷设避雷带做接闪器,网格不

大于10m×10m或12m×8m.突出屋面的金属物体(如铁爬梯、水管、透气管等),均与就近的避雷带相连.突出屋面的非金属物体(如烟囱等),加装独立小针,并与就近的避雷带相连。

(3)防侧雷击:建筑物应每层利用周边连通之圈梁钢筋作均压环;并将地面

45米以上外墙上的金属门窗、金属栏杆、幕墙金属构架等与均压环相连接。

(4)防雷引下线:利用外墙柱内2根不小于D16的钢筋为一组作引下线.引下线

间距不大于18米,上与避雷带,下与基础基地装置连接。

(5)防雷电波侵入措施:所有进入建筑物的电缆金属外皮、钢管及各种金属管

道应在进出口处就近与接地装置连接。垂直敷设的金属管道上下端与防雷系统连接。防雷击电磁脉冲保护措施:变压器高低压侧各相装设避雷器;各层主配电箱以及重要设备配电箱,屋顶的配电箱设浪涌保护器,并与防雷分界处作等电位连接;弱电机房配电箱以及进线处设浪涌保护器.

(6)接地装置: 利用基础内钢筋作接地装置,利用结构柱、地梁、桩基、底

板等内部主筋连通作自然接地体,结构基础钢筋(每处直径不小于16mm,根数不少于4根)。

中建三局建设工程股份有限公司(沪) - 3 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

1.3。2 接地设计

(1)本工程采用共用接地系统,即变压器中性点接地、保护接地及弱电系统

接地等共用防雷基础接地装置.接地电阻不大于1欧姆.

(2)大楼内电气线路采用TN-S接地系统。在变电所内设置总接地点,用100*100

*10的预埋钢板通过柱内主筋与基础钢筋连接。变电所内采用40 *4镀锌扁钢敷设接地干线,于墙上距地300mm明敷。接地干线与柱内预埋的接地连接钢板相焊接。配电柜底座槽钢、变压器外壳、低压PE干线均应与接地干线连接,变电所内设接地端子箱,变压器中性点接地单独采用40*4镀锡扁铜引至接地端子箱并与端子板联接。等电位接地端子板于墙上距地板面300mm安装。做法详国标D563。

(3)各弱电系统工作接地分别采用绝缘铜芯线引至接地端子箱。通过接地端子

箱与基础钢筋连接。

(4)等电位联结:建筑物内所有设备外露可导电部分和装置外可导电部分均应可

靠接地(PE),等电位联接作法详国标《等电位联接安装02D501—2》,具体的等电位联结设计部位及要求:

(8) 建筑物内所有管道井均设置接地端子;

(9) 电梯机房、强弱电机房以及电梯井、强弱电竖井均设置接地端子; (10) 用电设备集中的场所(如变配电间、水暖设备用房、配电间、弱电机

房等)均设置接地端子,以供设备、SPD等电位联结用; (11) 有水暖管道的安装通道设置接地端子;

(12) 接地预留端子选用国家定型产品,离地200mm明装,其与结构主

钢筋引下线的连接采用40x4镀锌扁钢焊接连通;

(13) 消防监控中心、弱电中心机房、售票机房等电子信息系统机房的等

电位联结采用M型结构设计,电子信息设备除连接PE线作为保护接地外,还采用两条不同长度的导线以最近距离与等电位联结网络连接。机房内所有设备的金属外壳、金属线槽、各类金属管道、建筑物金属结构、防静电地板等均须进行等电位联结并接地。

中建三局建设工程股份有限公司(沪) - 4 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

(14) 接地电阻检测 本项目每栋建筑物均设置不少于2处接地电阻测试

端子板,接地电阻测试端子板在室外离地0.5米嵌墙暗装,与建筑装饰相一致,并有可靠的防腐措施和明显的接地标志。

2施工部署

2。1人员组织结构

管理组织机构如下图:

安装经理 王涛 技术负责人 张海军 现场负责人 周学军 电气施工员 袁铭骏、兰吉永 施工班组长 金立强 2.2 施工进度计划

防雷接地系统工程工期根据施工前总包方提出的总体施工进度要求进行,配合其他专业施工队伍的进度,在现场具备防雷接地施工条件的前提下,在不影响其他施工的情况下完成防雷接地的施工工作。

中建三局建设工程股份有限公司(沪) - 5 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

2.3 劳动力计划

根据工程各部位的预算用工量和计划工期,在施工期间,根据工程施工进度要求,统一调整技术力量及劳动力。确保施工质量及工程进度.见下表:

序号 1 2 3 工 种 电工 电焊工 综合工 配合阶段(人) 安装高峰阶段(人) 收尾阶段(人) 2 2 1 2 4 2 1 1 2 2。4 施工机具

按照施工计划,将开工前及开工后近期需使用的施工机具及时组织进场,以确保工程按期完成。

见下表: 名称 电焊机(BX1—500型) 切割机 电锤 手枪钻 角向磨光机 剪线钳 接地电阻测试表(ZC29B—2型) 其他工具 单位 台 把 把 把 台 台 只 批 数量 2 1 1 1 4 2 2 1 2.5 施工材料计划

材料计划如下表: 序号 1 2 3 4 5 材料名称 镀锌扁钢 钢锌扁钢 镀锌圆钢 镀锌圆钢 钢板 规格型号 —40*4 —25*4 φ10 φ12 单位 米 米 米 米 数量 / / / / / 3施工方案

3。1 施工流程

接地端子预留 100*100*10 KG 接地装置安装 人员设备进场 中建三局建设工程股份有限公司(沪) - 6 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

防雷引下线安装 均压环及门窗接地安装 接地电阻测试箱安装 接闪器安装 接地电阻测试 变配电房及弱电机房接地 建筑物等电位联结 3.2 接地装置安装

本工程利用建筑物基础钢筋作为接地装置。利用结构柱、地梁、桩基、承台等内部的主筋连通做自然接地体,结构基础钢筋(每处直径不小于16mm,根数不不少于4根)一律采用焊接方式进行可靠连接。

3.2。1 接地网干线内主筋的跨接

根据施工图纸,找出接地网干线所在轴线,待结构底板内的地梁或面筋安装完毕,按接地网所在轴线,挑选4根地梁或面筋内直径大于16mm的主筋做接地干线连通。在有高低落差的地段,横筋与横筋之间用不小于最细一根横筋的圆钢搭接,或用相同截面积的扁钢连接,在主筋螺纹连接处用不小于Φ12的圆钢做跨接处理。并在接地干线纵横交叉处,横筋与纵筋进行连通跨接.

图1 横筋螺纹连接处跨接处理 图2 纵横筋跨接示意图

3。2。2接地网干线与桩基主筋的搭接

于接地干线交叉处,每个承台选2个桩基,每个桩基选2根主筋,利用¢12圆钢引4根桩基主筋与接地干线4根横筋焊接,以保证整个地网可靠连通及满足接地电阻要求。

图3 桩基内主筋与接地横筋的跨接

施工时,密切配合土建施工进度,首先保证横筋是通筋,在土建验筋合格后,在组合柱处横筋与竖筋可靠焊接。焊接时,搭接长度应符合施工工艺的要求。

中建三局建设工程股份有限公司(沪) - 7 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

3。2.3接地装置的电阻测试

接地装置安装完毕后应进行接地电阻的测试工作。接地电阻测试仪采用ZC28B-2型并应取得杭州地方相关检测部门检测合格后,进行测试。测试电阻应不大于1欧姆,如果多次测试未能满足要求,应增设人工接地极,直至接地电阻满足设计要求为止。

图4 接地电阻测试仪的接线图

3。3 接地端子预留

根据接地设计要求,电梯基坑、设备用房等位置需预留接地端子。

3。3。1 定位

根据施工图纸,找出需要设置接地端子的位置。然后从该位置附近找出与之最近的接地主筋。然后利用结构内主筋由接地装置引上至接地端子所在位置.

图5 接地端子扁钢接地点引出示意图

3.3.2 利用圆钢做过渡跨接引出

考虑结构内主筋多为螺纹钢,在与扁钢焊接时,难以保证焊接质量,采取用圆钢过渡跨接.待结构浇筑完毕后露出混泥土部分应做好防腐处理。

图6 利用圆钢过渡跨接

3.4 防雷引下线安装

利用柱内2根直径不小于16mm的结构主筋为一组作引下线。引下线间距不大于18米,上与避雷带,下与基础基地装置连接。

根据施工图纸,找出引下线所在柱子位置。待土建横梁调整完毕后,进行引下线竖筋与接地网横筋的跨接。被作为引下线的结构主筋要做好油漆标示,主筋套丝处应做好圆钢跨接,通长引上至屋面。上与避雷接闪器焊接,下与接地装置焊接。

图7 接地横主筋与引下线的跨接示意图

中建三局建设工程股份有限公司(沪) - 8 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

3.5 均压环及门窗接地的安装

根据设计要求,建筑外围一圈应利用圈梁钢筋做均压环;地面45米以上外墙上的金属门窗、金属栏杆、幕墙金属构架等与均压环相连接。沿建筑外围梁内2根圈梁主筋通长连通,横筋与横筋之间要保持通长连通,在主筋螺纹连接处用不小于Φ12的圆钢做跨接处理。

图8 防雷引下线与被利用做均压环的圈梁主筋的跨接示意图 图9 铝合金窗框的接地做法 图10 金属门框的接地做法 图11 扶手或栏杆接地做法

3。6 接地电阻测试箱的安装

接地测试箱按照图纸位置暗装在距室外地面0。8米处,用¢12镀锌扁钢与防雷引下线焊接后引入接地测试箱,扁钢进箱不少于8cm,扁钢上打不小于ф8mm圆孔后预留镀锌螺栓.测试箱加盖面板,做出接地标志。

图12 暗装接地电阻测试箱做法

3.7 接闪器施工

本工程属二类防雷建筑物,天面采用避雷带(明敷)及屋面板内结构主筋组成的避雷网格(间距不超过10m×10m或12m×8m)防止直击雷,明敷避雷带采用Φ12镀锌圆钢,支持卡间距不超过1.5m转弯处不超过0.5m,避雷带及避雷网格均须与防雷引下线做好焊接连通。

3。8变配电房及弱电机房接地

根据设计图纸要求,弱电机房和配电室做均压等电位连接,沿室内周围敷设一圈40X4热镀锌扁钢作为均压带,室内各接地点就近与均压带连接,形成M型接地。因此,需要事先向室内引入接地点(不少于两点),并保证接地点在墙面及地板完成后还能找出。

中建三局建设工程股份有限公司(沪) - 9 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

3。9 建筑物等电位连接

(1)公用设施的上、下水、煤气等金属管道、建筑物金属结构采用—40×4镀锌扁钢由总等电位箱(MEB)引至进户钢管处,采用等电位卡子与钢管连接。并在连接处引出-40x4扁钢引至接地母带与其可靠焊接。

(2) 户内卫生间局部等电位箱采用-25×4镀锌扁钢,由最近处接地干线焊接引至卫生间局部等电位箱,扁钢与箱内铜排采用ф8螺栓连接.局部等电位箱按照图纸位置暗装在距地面0.3米处。

4.0接地电阻测试

在防雷接地网系统连接形成后,接地电阻进行测试,要求测试电阻不大于1欧姆。并做好相应的记录。然后申请杭州市防雷检测站进行测试验收。

4质量保证措施

4。1 质量及工艺标准

4。1。1 钢材连接搭接倍数要求

钢质接地装置宜采用焊接连接,其搭接长度应符合下列规定: 1、扁钢与扁钢搭接为扁钢宽度的2倍,三面施焊; 2、圆钢与圆钢搭接为圆钢直径的6倍,双面施焊; 3、圆钢与扁钢搭接为圆钢直径的6倍,双面施焊;

4、扁钢和圆钢与钢管、角钢互相焊接时,除应在接触部位两侧施焊外,还应增加圆钢搭接件;

5、焊接部位除埋在混凝土外均作防腐处理。

接地装置连接应可靠,连接处不应松动、脱焊、接触不良.均压环与金属管道等自然接地体的连接,应采用焊接。如焊接有困难时,可采用卡箍连接,但应有良好的导电性。

中建三局建设工程股份有限公司(沪) - 10 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

4.1。2 各类焊接的要求

e) 平焊 

选择合适的焊接工艺,焊条直径,焊接电流,焊接速度,焊接电弧长度等,

通过焊接工艺试验验证。 

清理焊口:焊前检查坡口、组装间隙是否符合要求,定位焊是否牢固,焊

缝周围不得有油污、锈物。 

烘焙焊条应符合规定的温度与时间,从烘箱中取出的焊条,放在焊条保

温桶内,随用随取。 

焊接电流:根据焊件厚度、焊接层次、焊条型号、直径、焊工熟练程度

等因素,选择适宜的焊接电流。 

引弧:角焊缝起落弧点应在焊缝端部,宜大于10mm,不应随便打弧,

打火引弧后应立即将焊条从焊缝区拉开,使焊条与构件间保持2~4mm间隙产生电弧。对接焊缝及对接和角接组合焊缝,在焊缝两端设引弧板和引出板,必须在引弧板上引弧后再焊到焊缝区,中途接头则应在焊缝接头前方15~20mm处打火引弧,将焊件预热后再将焊条退回到焊缝起始处,把熔池填满到要求的厚度后,方可向前施焊。 

焊接速度:要求等速焊接,保证焊缝厚度、宽度均匀一致,从面罩内看

熔池中铁水与熔渣保持等距离(2~3mm)为宜。 

焊接电弧长度:根据焊条型号不同而确定,一般要求电弧长度稳定不变,

酸性焊条一般为3~4mm,碱性焊条一般为2~3mm为宜. 

焊接角度:根据两焊件的厚度确定,焊接角度有两个万面,一是焊条与

焊接前进方向的夹角为60~75°;二是焊条与焊接左右夹角有两种情况,当焊件厚度相等时,焊条与焊件夹角均为45°;当焊件厚度不等时,焊条与较厚焊件一侧夹角应大于焊条与较薄焊件一侧夹角。 

收弧:每条焊缝焊到末尾,应将弧坑填满后,往焊接方向相反的方向带弧,

使弧坑甩在焊道里边,以防弧坑咬肉。焊接完毕,应采用气割切除弧板,并修磨平整,不许用锤击落。 

清渣:整条焊缝焊完后清除熔渣,经焊工自检(包括外观及焊缝尺寸等)

确无问题后,方可转移地点继续焊接.

中建三局建设工程股份有限公司(沪) - 11 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

f) 立焊:    

基本操作工艺过程与平焊相同,但应注意下述问题: 在相同条件下,焊接电源比平焊电流小10%~15%。 采用短弧焊接,弧长一般为2~3mm。

焊条角度根据焊件厚度确定。两焊件厚度相等,焊条与焊条左右方向夹

角均为45°;两焊件厚度不等时,焊条与较厚焊件一侧的夹角应大于较薄一侧的夹角。焊条应与垂直面形成60°~80°角,使电弧略向上,吹向熔池中心。 

收弧:当焊到末尾,采用排弧法将弧坑填满,把电弧移至熔池中央停弧。

严禁使弧坑甩在一边.为了防止咬肉,应压低电弧变换焊条角度,使焊条与焊件垂直或由弧稍向下吹。 g) 横焊: 

基本与平焊相同,焊接电流比同条件平焊的电流小10%~15%,电弧长

2~4mm.焊条的角度,横焊时焊条应向下倾斜,其角度为70°~80°,防止铁水下坠。根据两焊件的厚度不同,可适当调整焊条角度,焊条与焊接前进方向为70°~90°。 h) 仰焊

基本与立焊、横焊相同,其焊条与焊件的夹角和焊件厚度有关,焊条与焊接方向成

70°~80°角,宜用小电流、短弧焊接。

4.2 质量通病及防治措施

1、尺寸偏差

扁钢焊接时应严格控制其相对位置,扁钢组对应有专人进行,合格后方准焊接。 2、焊瘤

a)熔池下部出现“小鼓肚”时,可利用焊条左右摆动和挑弧动作加以控制。

b)在搭接接头立焊时,焊接电流应比平焊适当减少,焊条左右摆动时在中间部位走的快些,两边稍慢些。 3、咬边

选用合适的电流,避免电流过大.操作时电弧不能拉的过长,并控制好焊条的角度和运弧的方法。

4、引上线的制作有专人负责,连接要同侧、同标高。色带宽度、方向一致。 5、过变形缝、沉降缝处的接地干线及避雷带要做补偿处理。

中建三局建设工程股份有限公司(沪) - 12 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

4。3质量保证措施

4。1.1按照国家有关安装工程施工及验收规范以及杭州市有关规定进行验收,按“建筑安装工程质量评定统一标准(GBJ300—88)”进行质量评定.

4.1.2 必须严格按图纸及施工方案施工,施工方案必须经监理批准。 4。1.3 对施工班组进行技术交底,必须交到每一个操作工人.

4.1。4 每道工序完成后,必须经过自检合格后,报请相关工长验收,工长验收合格后,请质量员验收,质量员验收合格后,报请监理工程师验收,合格后,方可进行下一道工序的施工。同时,班组间应进行交接检,交接检后方可进入下一道工序施工。

4。1。5 土建砼浇筑前,必须接到有机电部经理签字的工序交接单后方可进行砼浇筑。

4.1.6 隐蔽工程必须经过质量员,业主,监理及设计单位验收合格并签字后方可隐蔽。 4.1.7 材料进场前必须提供相应的样品,经监理及业主批准后方可进场。进场后经相关责任师、监理、业主验收合格后方可用于施工,同时应提供相应产品检测报告及合格证等。

5安全及文明施工

5。1 安全施工

5。1。1 工人进场必须接受项目经理部组织的安全教育及安全考核。 5。1.2 必须对工人进行安全交底,必须有每一个工人的签名。 5.1.3 每天上班前应开班前会,并有记录.

5.1。4 各项作业指挥及操作必须严格按照国家、浙江省、杭州市、公司及项目经理部有关的安全法律、法规、操作规程及规章制度执行.

5。1。5 进入现场必须戴安全帽,系好帽带,穿安全鞋。高空作业必须系安全带. 5.1。6 施工地点及附近的洞口必须封堵,防止高空坠落。 5。1.7 施工现场严禁吸烟,严禁饮酒,不许打架,戏闹。 5.1。8 不许翻越栏杆。严禁从高处向下扔东西。

5.1。9 现场接电必须由专职维护电工进行,严禁私拉乱接.

中建三局建设工程股份有限公司(沪) - 13 -

杭州铁路东站西广场•机电安装工程 防雷接地工程施工方案

5.1。10 电线、电缆等不许拖地。

5.1。11 使用手持电动工具前必须检查其性能,保证良好。 5.1。12 特种作业必须持证上岗.

5.1.13 电气焊施工前必须开动火证,有专人看火,带灭火器.

5。1.14 电焊机不许放置在雨中及潮湿地面上。电焊机必须双线到位. 5。1。15 潮湿地点作业应穿绝缘胶鞋。 5。1.16 施工照明必须使用36V低压电。

5。2 文明施工

5.2。1 进入施工现场必须佩带出入证. 5.2.2 进入现场应衣帽整齐。 5。2.3 施工现场严禁随地大小便。

5。2。4 施工完毕应作到“工完场清\"。不许乱丢垃圾. 5。2。5 施工现场应做好自身及其他专业的成品保护工作。

5。2.6 施工材料应设置专门仓库或放置在指定堆放场地上,严禁四处乱堆材料。 5。2。7 材料应码放整齐,并挂好标识牌。

中建三局建设工程股份有限公司(沪) - 14 -

因篇幅问题不能全部显示,请点此查看更多更全内容